Product Details:
Material | Rubber |
Color | Black |
Thickness | 2 mm |
Insulating Mats for Electrical Purposes IS:15652/2006
(With Latest Amendments)
Safety Insulation Mats as per IS:15652 Superseding IS:5424/69 was introduced in the the year 2007, with the view of technical advancement & more stringent Industrial safety parameters. Insulating mats safeguard life of Electricians & other Technicians, in case of any accidental current leakage while working on AC or DC installations. Synthetic Insulation mat confirms complete safety of workers handling Live electronic equipments.
Material Composition:
Made of Dielectric “Elastomer” which possess elastic properties and may be natural or synthetic in nature. Typically a combination of rubber & Synthetic Polymers.
Specification:
Safety Mats for Electrical Applications are divided in to three main classes based on Voltage Ratings. Recommended division is as follows:
VOLTAGE RATINGS | ||||
Class | Thickness | Working Voltage | Proof voltage | Break Down Voltage |
A | 2.0 mm | 3.3KV | 10KV | 30 KV |
B | 2.5 mm | 11KV | 22KV | 45 KV |
C | 3.0 mm | 33KV | 36KV | 65 KV |